Viessmann · Boiler troubleshooting
Water side piping with Vitotronic control
What is going on
Use a spring-loaded flow-check valve in heating circuits without mixing valves, to prevent gravity circulation of heat into the system in summer. Flush the system before connecting.
Likely causes
- Sludge left in an older system settling in the boiler
Check in this order
- Flush the heating system thoroughly, especially older systems.
- Install a spring-loaded flow-check valve in circuits without mixing valves.
- Remove the top back panel before connecting pipe fittings.
- Connect the system supply to the supply connection with NPT fittings.
- Connect the system return to the return connection with NPT fittings, using the return injector.
- Install the gauge with brass extension coupling in the 1/2 in opening.
Applies to: Vitorond 100 VR1 with Vitotronic control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.