Viessmann · Boiler troubleshooting

Water side piping with Vitotronic control

Vitorond 100

What is going on

Use a spring-loaded flow-check valve in heating circuits without mixing valves, to prevent gravity circulation of heat into the system in summer. Flush the system before connecting.

Likely causes

  • Sludge left in an older system settling in the boiler

Check in this order

  1. Flush the heating system thoroughly, especially older systems.
  2. Install a spring-loaded flow-check valve in circuits without mixing valves.
  3. Remove the top back panel before connecting pipe fittings.
  4. Connect the system supply to the supply connection with NPT fittings.
  5. Connect the system return to the return connection with NPT fittings, using the return injector.
  6. Install the gauge with brass extension coupling in the 1/2 in opening.

Applies to: Vitorond 100 VR1 with Vitotronic control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.