Weil-McLain · Boiler troubleshooting
Reducing maximum pipe length for extra elbows
What is going on
Each elbow beyond the allowed count reduces the maximum vent or air length. Use the pipe manufacturer's figure if it is longer.
Check in this order
- Count all elbows in the vent and air piping, including terminations.
- Allowed without reduction two elbows in the vent piping and one in the air piping.
- For each extra elbow (45 or 90 degree), reduce 6 in pipe by 15 ft.
- For each extra elbow, reduce 8 in pipe by 7 ft.
- If the pipe maker lists a longer equivalent length for the elbow, use that value.
Applies to: Vent and air piping layout
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.