Gas supply connection and leak check

I-Series Plus

What is going on

Gas connection must be done by a licensed professional. Confirm gas type and supply pressure before connecting. Convert the gas type with the included conversion kit if it does not match the building supply (see Appendix section 14.5). Check supply pressure at the gas company's upstream location with all gas appliances running; it must be within the specification limits in section 3.4.

Likely causes

  • Wrong gas type causes injury or unit damage
  • Undersized gas line can lose pressure under full demand

Check in this order

  1. Turn off 120V power and turn off the gas before working on the connection.
  2. Confirm the gas type matches the building supply; convert with the included kit if it does not.
  3. Check supply pressure upstream with all gas appliances operating and compare it to section 3.4.
  4. Install a sediment trap upstream of the gas controls.
  5. Install a manual gas shutoff valve between the gas supply and the boiler.
  6. Keep the gas ignition components protected from dripping, spraying and rain during operation and service.
  7. Purge debris from the gas line before connecting it to the boiler.
  8. Use approved connectors and a thread compound that resists LPG (propane).
  9. Check all joints for gas tightness with soap, leak detector solution or equivalent. Rinse with water after testing unless the solution is known to be non-corrosive.
  10. Do not operate the boiler if a leak is found until the leak is repaired.
  11. Size the gas line for the full demand of the boiler and all other gas appliances using section 6.3.

Applies to: Gas supply piping to the boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation manual, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.