Burner does not switch on (Vitotronic 100, GC1)
What is going on
The boiler burner stays off. Check the heating program first, then the draught device and flue damper.
Likely causes
- Heating program 9 is set (its button is lit)
- Vitoair draught stabilizer defective (pressure jet burners only)
- Motor-controlled flue gas damper failed (gas boilers with atmospheric burner)
Check in this order
- Set the 'rw' heating program (see page 10).
- If the Vitoair draught stabilizer is defective, inform the heating contractor.
- To run the Vitoair in manual mode, press in rotary knob A on the motor and turn it fully beyond setting 4.
- If the flue gas damper has failed, inform the heating contractor.
- To run the flue gas damper in manual mode, press in rotary knob A on the motor and turn it fully beyond setting 4.
Applies to: Vitotronic 100 GC1 on Viessmann boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.