Weil-McLain · Boiler troubleshooting

Direct exhaust venting: approved components

CGi Series 5

What is going on

Direct exhaust uses inside combustion air and a pressurized Category III vent. Every joint must be sealed. Use only a listed 3 inch vent system.

Check in this order

  1. Choose one listed vent manufacturer Heat-Fab Saf-T Vent, Metal-Fab CORR/GUARD, Z-Flex Z-Vent, or ProTech FasNSeal.
  2. Use the vent starter from that same manufacturer. Never mix components from different systems.
  3. Check maximum run length and elbow count against the vent length table. Do not exceed it. The termination fitting is not counted as an elbow.
  4. Select all vent components, including the vent starter, from the same manufacturer.
  5. Minimum run is 2 ft equivalent with two elbows.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.