Viessmann · Boiler troubleshooting
Reset manual reset temperature limit switches
What is going on
The supply water and flue gas temperature limit switches lock out mechanically when the probe temperature goes over the limit. The switches are factory preset and must not be adjusted.
Likely causes
- Probe temperature exceeded the limit setpoint
Check in this order
- Confirm the probe has cooled by about 14 F (8 C) below the limit temperature.
- Unscrew the reset cap and set it aside.
- Press to reset the switch.
- Reinstall the reset cap.
- If the switch will not reset, replace the switch.
Applies to: CA3B Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 59. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.