Viessmann · Boiler troubleshooting

Read temperatures and quick scans

Vitotronic 200-H

What is going on

Lists the values that can be read, depending on the equipment fitted: slope and shift for M1/M2/M3, outdoor temperature (set and actual), sensor 17B, DHW set and actual temperatures (including second DHW sensor), supply temperature set/actual, room temperature set/actual, and quick scans 1 to 9. Also shows software versions and bus or LON participant data for each module. Pressing D resets the adjusted outdoor temperature to the current outdoor temperature. Some values only appear when the matching sensor or remote control is connected.

Check in this order

  1. Press 9 and the rw key together for about 2 seconds.
  2. Select the required scan with the arrow keys.
  3. Press OK to finish the scan.

Applies to: Vitotronic 200-H

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H installation and service instructions, p. 21-22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.