Commissioning check-out highlights before handover
What is going on
Key verifications from the startup checklist. Complete full checklist and certificate on page 140.
Check in this order
- Confirm the U-Control is set for the correct boiler model and installation date/contact entered.
- Confirm boiler and heat distribution units are filled, water chemistry is verified, and inhibitor added.
- Purge air from system and from gas piping; check gas piping for leaks; confirm condensate trap is primed.
- Confirm propane orifice and propane conversion label if firing propane.
- Check thermostat circuit wiring for stray voltages.
- Verify burner flame and combustion per page 40.
- Verify space heating and DHW control operation; test any field-installed limits or low water cutoff for proper lockout.
- Cycle the boiler with the thermostat at highest and lowest settings and confirm startup and shutdown.
- Measure natural gas input and check incoming gas pressure (see gas pressure setting).
- Observe several operating cycles, set room thermostat, and fill out the Installation and Service Certificate.
Applies to: Ultra Series 4 startup
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.