Viessmann · Boiler troubleshooting
Check and replace burner refractory ring and cylinder burner
What is going on
Inspect the burner refractory ring and cylinder burner assembly for damage. Replace if damaged.
Likely causes
- Damaged refractory ring or cylinder burner
Check in this order
- Remove the electrode block and ionization electrode.
- Undo the three retaining clips and remove the refractory ring.
- Loosen the four Torx screws and remove the cylinder burner assembly and assembly gasket.
- Fit the new cylinder burner assembly and new gasket. Tighten to 3.3 lb.ft. (4.5 Nm) with a calibrated torque wrench.
- Refit the refractory ring and secure with the retaining clip.
- Refit the electrode block and ionization electrode. Tighten to 2.6 lb.ft. (3.5 Nm) with a calibrated torque wrench.
Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.