Viessmann · Boiler troubleshooting

External demand via switching contact

Vitotronic 300 GW6B

What is going on

Starts the burner on an external floating contact, subject to load. Connection is on plug aVH.2/aVH.3, or on the EA1 extension.

Check in this order

  1. Use a potential-free contact only.
  2. Single boiler when the contact closes, the burner runs subject to load and heats to the boiler water setpoint in coding 9b (General group). Limiting is done by that setpoint and by the boiler water maximum in coding 06 (Combustion Controller group).
  3. Multi boiler when the contact closes, each boiler burner runs subject to load and heats to the supply setpoint in coding 9b. Limiting is done by that setpoint and the supply maximum in coding 37 (Cascade group).
  4. Plug aVH no coding change needed.
  5. EA1 extension set 5d (DE1), 5e (DE2) or 5f (DE3) in the General group to 2.

Applies to: Single boiler and cascade control units

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service manual, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.