Viessmann · Boiler troubleshooting
Fixed high limit test (CSD-1)
What is going on
Used to check the manual reset fixed high limit. The fixed high limit should trip at 210 °F (99 °C) and produce an F2 fault. The manufacturer is not responsible for damage caused by overheating the system during this test.
Check in this order
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover from the back of the boiler control to access the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Once the burner ignites, unplug the boiler pump plug sÖ from the boiler control board, gently with pliers.
- Watch the boiler temperature on the control display until the burner shuts off.
- If the limit temperature is not reached, two minutes after the burner shuts off, plug the boiler pump in for a maximum of 1 second. Repeat the test.
- Confirm the fixed high limit trips at 210 °F (99 °C) and produces an F2 fault.
Applies to: Vitodens 200-W B2HB boilers where CSD-1 testing is required
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.