Viessmann · Boiler troubleshooting

Fixed high limit test (CSD-1)

Vitodens 200-W

What is going on

Used to check the manual reset fixed high limit. The fixed high limit should trip at 210 °F (99 °C) and produce an F2 fault. The manufacturer is not responsible for damage caused by overheating the system during this test.

Check in this order

  1. Make sure the boiler and boiler pump are in normal operating condition.
  2. Remove the cover from the back of the boiler control to access the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Once the burner ignites, unplug the boiler pump plug sÖ from the boiler control board, gently with pliers.
  5. Watch the boiler temperature on the control display until the burner shuts off.
  6. If the limit temperature is not reached, two minutes after the burner shuts off, plug the boiler pump in for a maximum of 1 second. Repeat the test.
  7. Confirm the fixed high limit trips at 210 °F (99 °C) and produces an F2 fault.

Applies to: Vitodens 200-W B2HB boilers where CSD-1 testing is required

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.