Rinnai · Boiler troubleshooting
Manual CH plumbing flush and purge
What is going on
Flush the heating system with approved cleaner before adding a new boiler when replacing an existing one. Clean the dirt trap, then purge the boiler and system.
Likely causes
- Scale and sludge in the heating system
Check in this order
- Disconnect power and turn off gas.
- Add an approved cleaner and follow its directions. Run the boiler in DHW or heating for 3 days.
- Flush the boiler and system and clean the dirt trap.
- Add an approved inhibitor (recommended).
- Purge the system close supply shutoff #3 and boiler valves #1 and #2, open autofill to at least 20 PSI, then flush through hose #2 with boiler drain #4 open.
- Purge the boiler keep valves #1 and #3 closed, open #2, close #4, and flush through hose #1 with autofill at least 20 PSI.
- Continue purging until no bubbles show in the bucket.
- Run the boiler in its deaeration program per the deaeration section.
Applies to: All I-Series Plus condensing combi boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 121. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.