Manual CH plumbing flush and purge

I-Series Plus

What is going on

Flush the heating system with approved cleaner before adding a new boiler when replacing an existing one. Clean the dirt trap, then purge the boiler and system.

Likely causes

  • Scale and sludge in the heating system

Check in this order

  1. Disconnect power and turn off gas.
  2. Add an approved cleaner and follow its directions. Run the boiler in DHW or heating for 3 days.
  3. Flush the boiler and system and clean the dirt trap.
  4. Add an approved inhibitor (recommended).
  5. Purge the system close supply shutoff #3 and boiler valves #1 and #2, open autofill to at least 20 PSI, then flush through hose #2 with boiler drain #4 open.
  6. Purge the boiler keep valves #1 and #3 closed, open #2, close #4, and flush through hose #1 with autofill at least 20 PSI.
  7. Continue purging until no bubbles show in the bucket.
  8. Run the boiler in its deaeration program per the deaeration section.

Applies to: All I-Series Plus condensing combi boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 121. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.