Viessmann · Boiler troubleshooting

Heating circuit frost protection

Vitotronic 200

What is going on

With outdoor temperatures below 34 F / 1 C the control keeps the supply temperature at 59 to 72 F / 15 to 22 C for frost protection. The frost threshold can be changed with coding A3. Setting A3 below 34 F / 1 C risks freezing pipes outside the insulated area, such as roof space, garages and radiator alcoves. Check the insulation of the whole system and watch standby periods such as holidays.

Check in this order

  1. Check the insulation of exposed piping before lowering the frost threshold below 34 F / 1 C.
  2. Set coding A3 to the required threshold value.
  3. Use coding A4:1 to switch off frost protection only if coding A3:-9 is set.

Applies to: Heating circuit frost protection, codings A3 and A4

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 KW2 service instructions, p. 48, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.