Category II negative pressure aids: fan, damper and spill switch

SVF Series 1

What is going on

Where natural draft cannot keep the required negative pressure at the boiler outlet, Weil-McLain recommends added draft or flow control devices. Improper positive pressure can cause CO spillage.

Likely causes

  • Higher efficiency of the SVF gives lower exhaust temperatures and less natural draft

Check in this order

  1. If natural draft cannot hold the negative pressure range, consider a variable speed chimney fan or power venter.
  2. Wire a flow proving switch into the closure switch on terminal block P11.
  3. Consider a double acting barometric damper or modulating damper to hold the negative pressure range.
  4. When using any damper, add a thermal spill switch to detect exhaust flow into the boiler room.
  5. Confirm the thermal spill switch temperature range suits the SVF flue gas temperature.
  6. Let the system designer set the spill switch set-point per local authority requirements.

Applies to: Category II vent systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 Boiler Manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.