Weil-McLain · Boiler troubleshooting

Check temperature sensors with an ohmmeter

ECO Tec Series 3

What is going on

Compare sensor resistance against the reference table.

Likely causes

  • Open or shorted sensor wiring or a failed sensor.

Check in this order

  1. Measure sensor resistance at 32 F, 60 F, 70 F and 212 F (ice point, room temperature and boiling point).
  2. Compare readings with the sensor resistance table.
  3. For a control check, connect a resistance decade box in place of the sensor and confirm the display temperature matches the input resistance.
  4. For dual sensors, confirm the two temperatures are within 10 F.

Applies to: Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 160. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.