Check temperature sensors with an ohmmeter
What is going on
Compare sensor resistance against the reference table.
Likely causes
- Open or shorted sensor wiring or a failed sensor.
Check in this order
- Measure sensor resistance at 32 F, 60 F, 70 F and 212 F (ice point, room temperature and boiling point).
- Compare readings with the sensor resistance table.
- For a control check, connect a resistance decade box in place of the sensor and confirm the display temperature matches the input resistance.
- For dual sensors, confirm the two temperatures are within 10 F.
Applies to: Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 160. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.