Multiple boiler cascade piping

Vitocrossal 200 CI2

What is going on

Cascade systems can have up to 16 Vitocrossal 200 CI2 boilers. Each boiler must be isolatable from the heating system with its own boiler isolation valve. The lead boiler carries the common supply temperature sensor TSI, which can be on a low-loss header or a common supply. Use the applicable multiple-boiler technical documentation and contact Viessmann sales for help with the design. Systems with constant boiler or system pumps may need a hydronic pressure bypass. Common cascade layouts can include a BMS connection (BACnet or Modbus).

Check in this order

  1. Install a boiler isolation valve on every boiler in the cascade.
  2. Place the common supply temperature sensor TSI on the lead boiler.
  3. Add a hydronic pressure bypass if constant boiler or system pumps are used.
  4. Use the multiple-boiler documentation for design and contact Viessmann sales for assistance.

Applies to: Vitocrossal 200 CI2 multiple-boiler systems, up to 16 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.