Size gas supply for natural gas

SVF 500/600 Series 1

What is going on

Sizing approach for natural gas supply to the boiler.

Check in this order

  1. Measure the straight pipe run from the meter outlet to the boiler inlet.
  2. Add the equivalent length of each fitting to that run to get total pipe length.
  3. Add up the input of all connected appliances in Btuh and divide by 1,000 to get approximate cubic feet per hour.
  4. Pick the pipe size from the capacity table that meets that flow at the total length.
  5. Confirm the regulator is 100% lock-up and that the pipe meets local code (ANSI Z223.1/NFPA 54 or CAN/CSA B149.1).

Applies to: Natural gas supply piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.