Viessmann · Boiler troubleshooting
Burner control unit fault lamp on after start-up
What is going on
The fault lamp on the control unit lights and the display on the burner control unit blinks. This is usually a reset issue. If the fault returns, the gas supply to the combination gas valve may be blocked after work on the gas pipe. During initial start-up there may not be enough gas in the pipe, which also causes a fault.
Likely causes
- Reset is needed on the burner control unit.
- Supply side of the combination gas valve blocked after gas pipe work.
- Insufficient gas in the gas pipe during initial start-up.
Check in this order
- Press the reset button R on the burner control unit.
- If the fault continues, check the gas supply side of the combination gas valve for blockage.
- If the fault came up during initial start-up, ventilate the gas line again.
- Reset the burner control unit again and refer to the burner control unit section.
- Expect the burner to start about 3 min after the fault clears.
Applies to: Vitocrossal 300 CA3B Dual Fuel, burner control unit reset
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.