Burner control unit fault lamp on after start-up

Vitocrossal 300 CA3B Dual Fuel

What is going on

The fault lamp on the control unit lights and the display on the burner control unit blinks. This is usually a reset issue. If the fault returns, the gas supply to the combination gas valve may be blocked after work on the gas pipe. During initial start-up there may not be enough gas in the pipe, which also causes a fault.

Likely causes

  • Reset is needed on the burner control unit.
  • Supply side of the combination gas valve blocked after gas pipe work.
  • Insufficient gas in the gas pipe during initial start-up.

Check in this order

  1. Press the reset button R on the burner control unit.
  2. If the fault continues, check the gas supply side of the combination gas valve for blockage.
  3. If the fault came up during initial start-up, ventilate the gas line again.
  4. Reset the burner control unit again and refer to the burner control unit section.
  5. Expect the burner to start about 3 min after the fault clears.

Applies to: Vitocrossal 300 CA3B Dual Fuel, burner control unit reset

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.