Viessmann · Boiler troubleshooting
Removing the burner
What is going on
Burner removal for service. If the programming unit is at the top, lower it into the maintenance position first (see p. 46). Same procedure for B1HE/KE 85/120 and 150/199.
Check in this order
- Turn off the ON/OFF switch.
- Close the gas shut-off valve and secure it against reopening.
- Disconnect the fan motor (2 plugs), ionization electrode, ignition unit and ground.
- Undo the gas supply pipe fitting, holding the fitting with an open-ended wrench.
- Undo the burner screws and remove the burner.
- Cover the gas connection on the 85/120 so small parts cannot fall in.
- Do not use pliers. Use the two-wrench method and make sure the corrugated gas line does not twist.
Applies to: B1HE/KE 85/120 and 150/199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.