Viessmann · Boiler troubleshooting

Check outdoor temperature sensor (NTC)

Vitotronic 300

What is going on

Test the outdoor sensor across plug terminals 1 and 2 and compare the result with the NTC curve. If the reading is far off, test the sensor again with the wires disconnected, then decide whether to replace the lead or the sensor. The curve values are not legible in the extracted pages.

Likely causes

  • Sensor resistance far from the curve
  • Faulty connecting lead

Check in this order

  1. Pull plug (outdoor sensor plug).
  2. Measure the resistance across terminals 1 and 2 and compare with the curve.
  3. If the result is very different, disconnect the wires from the sensor and repeat the test on the sensor.
  4. Replace the lead or the outdoor temperature sensor, depending on the result.

Applies to: Outdoor temperature sensor, Vitotronic 300 GW6B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 121. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.