Weil-McLain · Boiler troubleshooting
Display red or flashing red
What is going on
A red display means an error or limit event occurred. A flashing red display means lockout.
Likely causes
- Error or limit event
- Lockout condition
Check in this order
- Read the error on the display.
- If the display is flashing, the boiler is in lockout. Clear the cause before resetting.
- Reset from the control after the cause is cleared.
Applies to: SVF 1500-3000 Series 1 with Unity control
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 68. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.