Removing boiler from an existing common vent
What is going on
When an existing boiler is removed from a common vent, check that the remaining appliances still vent properly. Test with the other appliances running and the building set up as it would be under worst case.
Likely causes
- Spillage or backdraft from remaining appliances
- Blocked, undersized, corroded or leaking common vent
Check in this order
- Seal any unused openings in the common venting system.
- Inspect the vent for proper size, horizontal pitch, blockage, restriction, leakage and corrosion.
- Close exterior doors and windows and doors to other spaces. Turn on clothes dryers and exhaust fans at maximum speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Run the remaining appliance on continuous operation with the thermostat set high.
- Check for spillage at the draft hood relief opening after 5 minutes of main burner operation, using a match or candle flame.
- If the vent does not work correctly, resize it toward the minimum size from the National Fuel Gas Code Part 13 tables.
- Return doors, windows, fans, dampers and other appliances to their normal condition.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.