Removing boiler from an existing common vent

CGi Series 5

What is going on

When an existing boiler is removed from a common vent, check that the remaining appliances still vent properly. Test with the other appliances running and the building set up as it would be under worst case.

Likely causes

  • Spillage or backdraft from remaining appliances
  • Blocked, undersized, corroded or leaking common vent

Check in this order

  1. Seal any unused openings in the common venting system.
  2. Inspect the vent for proper size, horizontal pitch, blockage, restriction, leakage and corrosion.
  3. Close exterior doors and windows and doors to other spaces. Turn on clothes dryers and exhaust fans at maximum speed. Do not run a summer exhaust fan. Close fireplace dampers.
  4. Run the remaining appliance on continuous operation with the thermostat set high.
  5. Check for spillage at the draft hood relief opening after 5 minutes of main burner operation, using a match or candle flame.
  6. If the vent does not work correctly, resize it toward the minimum size from the National Fuel Gas Code Part 13 tables.
  7. Return doors, windows, fans, dampers and other appliances to their normal condition.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.