Install flow switch or combustion air damper proof of closure
What is going on
Remove the J18 jumper and wire the device as shown in the wiring diagram. Devices must provide isolated contacts.
Check in this order
- Remove the jumper on connector J18.
- Wire the flow switch and/or combustion air damper end switch in series to J18 as shown.
- For a CAD interlock, assign INPUT 3 as an AUX PUMP/OUTPUT function.
- Set the AUX PUMP/OUTPUT operating mode to local or System Damper so the damper opens whenever the boiler is called to fire.
- Connect OUTPUT 3 (120VAC) to the damper motor. Use an isolation relay if the damper needs another voltage or more than 2.2 A.
- For multi-boiler CAD interlock, wire all proof of closure inputs in series with the end point devices and each boiler's closure switch input.
- No control settings are required for a flow switch alone.
Applies to: ECO Tec Series 3 all models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.