Install flow switch or combustion air damper proof of closure

ECO Tec Series 3

What is going on

Remove the J18 jumper and wire the device as shown in the wiring diagram. Devices must provide isolated contacts.

Check in this order

  1. Remove the jumper on connector J18.
  2. Wire the flow switch and/or combustion air damper end switch in series to J18 as shown.
  3. For a CAD interlock, assign INPUT 3 as an AUX PUMP/OUTPUT function.
  4. Set the AUX PUMP/OUTPUT operating mode to local or System Damper so the damper opens whenever the boiler is called to fire.
  5. Connect OUTPUT 3 (120VAC) to the damper motor. Use an isolation relay if the damper needs another voltage or more than 2.2 A.
  6. For multi-boiler CAD interlock, wire all proof of closure inputs in series with the end point devices and each boiler's closure switch input.
  7. No control settings are required for a flow switch alone.

Applies to: ECO Tec Series 3 all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.