Viessmann · Boiler troubleshooting
External control: switch on 1st stage burner
What is going on
Dry contact at plug aVD starts the first burner stage.
Check in this order
- Connect a dry contact to terminals 1 and 2 of plug aVD.
- Contact closed 1st stage burner starts. 2nd stage runs only to hold minimum temperature (not with Vitocrossal 300).
- Contact open 1st stage burner stops.
Applies to: Two-stage burner, VD2/VD2A/CT3/CM2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.