NTI · Boiler troubleshooting

Clean the condensate trap

TRX150

What is going on

Clean the siphon cap, cone and ball. If the boiler has a condensate neutralizer kit, check it at the same time.

Check in this order

  1. Remove the condensate drain hose from the bottom of the boiler.
  2. From below the boiler, remove the siphon cap retaining clip.
  3. Depress the two lateral hinges on the siphon cap (use a tool if needed) and remove the cap.
  4. Remove the cone and the ball.
  5. Clean each part. Do not use solvents.
  6. Confirm all parts are present. If any part is missing, do not operate the boiler. Replace the entire condensate trap assembly.
  7. Refill the trap with clean water and reassemble in reverse order, making sure the siphon cap and clip are secure.
  8. If a neutralizer is fitted, check it and top up the limestone chips if needed. Chips must be no smaller than 1/2 inch.
  9. Check condensate piping for sags or leaks and repair before restoring power.
  10. If the boiler has a condensate pump, confirm it runs properly.

Applies to: TRX150

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI TRX150 manual, p. 97-98. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.