Check and adjust gas valve offset at low fire

NCB700

What is going on

Check the gas valve offset at low fire against the altitude kit table. Adjust only if the reading is out of range.

Likely causes

  • Offset reading is outside the range for the installed altitude kit

Check in this order

  1. Open the offset pressure port by loosening the screw two turns, or use the mechanical manometer port.
  2. Connect a manometer to the offset pressure port. On a dual port manometer, use the positive pressure side.
  3. Open several DHW fixtures on full hot.
  4. Set the boiler to 1-stage MIN mode (see 12.6.7 Setting the Special Operation Modes).
  5. Read the offset value at low fire and compare it to Table 3.
  6. If out of range, remove the screw-on cover over the gas valve set screw. The set screw is shown in Figure 10.
  7. Using a 5/32 in or 4 mm Allen wrench, turn the set screw no more than 1/4 turn. Clockwise raises the offset; counterclockwise lowers it.
  8. Recheck the offset at low fire.
  9. Do not check or adjust the offset at high fire.

Applies to: NCB700 gas valve, low fire offset

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 144. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.