Vent pipe installation

Vitorond 100

What is going on

Use approved vent material only. Keep the run short with few elbows. Support horizontal runs so they do not sag, and keep them as short as possible.

Check in this order

  1. Route the vent for the shortest path with minimum elbows.
  2. Fit the factory vent adaptor to the flue gas collar with three equally spaced corrosion-resistant self-tapping screws and high-temperature silicone, or equivalent.
  3. Connect the chimney through an 18 in (457 mm) field-supplied, slightly inclined intermediate section.
  4. Pitch horizontal runs up at least 1/4 in per ft from the boiler to the terminal.
  5. Support horizontal runs with metal strap every 4 ft (1.2 m).
  6. Seal all flue joints.
  7. Insulate any uninsulated vent pipe to reduce flue gas cooling and noise.

Applies to: Vitorond 100 VR1 oil-fired boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.