Viessmann · Boiler troubleshooting
Burner reassembly and final CO2 check
What is going on
Reassemble the burner and confirm combustion and gas tightness after dismantling.
Check in this order
- Position the burner plate with burner mesh on the 8 studs and tighten nuts to 7.3 lb.ft (10 Nm).
- Position the upper burner section and tighten M10 nuts to 7.3 lb.ft (10 Nm).
- Push on the ignition and ionization electrode connectors.
- Connect the plugs at the plug-in panel and burner control unit; connect mains plug last.
- Fit the gas connection pipe.
- Do not use leak detection spray near electrical contacts.
- Start the burner, run a function test and check the gas fitting for tightness.
- Take CO2 readings after each burner dismantling and record them in the maintenance record on page 158.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.