External mixing valve open / closed inputs
What is going on
Floating contacts on plug aVD that open or close the mixing valve of a heating circuit.
Check in this order
- Use a potential-free contact only.
- Wire the external 'mixing valve open' contact and the external 'mixing valve closed' contact to plug aVD.
- For 'mixing valve open', set coding 9a in the General group to assign the function to the heating circuits.
- For 'mixing valve closed', set coding 99 in the General group to assign the function to the heating circuits.
- Keep DC separation between the ground conductor and the negative pole of the on-site voltage source.
Applies to: Vitotronic 300 GW6B, plug aVD
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service manual, p. 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.