Viessmann · Boiler troubleshooting

External mixing valve open / closed inputs

Vitotronic 300 GW6B

What is going on

Floating contacts on plug aVD that open or close the mixing valve of a heating circuit.

Check in this order

  1. Use a potential-free contact only.
  2. Wire the external 'mixing valve open' contact and the external 'mixing valve closed' contact to plug aVD.
  3. For 'mixing valve open', set coding 9a in the General group to assign the function to the heating circuits.
  4. For 'mixing valve closed', set coding 99 in the General group to assign the function to the heating circuits.
  5. Keep DC separation between the ground conductor and the negative pole of the on-site voltage source.

Applies to: Vitotronic 300 GW6B, plug aVD

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service manual, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.