Viessmann · Boiler troubleshooting

Cleaning the combustion chamber and heating surfaces

Vitocrossal 300 CA3B Dual Fuel

What is going on

Clean the stainless steel heat exchanger and combustion chamber without damaging the surfaces. Discoloration of the heat exchanger is normal and does not affect performance.

Likely causes

  • Sediment buildup on heat exchanger
  • Debris in combustion chamber

Check in this order

  1. Check gaskets, sealing rope and thermal insulation parts for damage; replace any damaged parts.
  2. Vacuum loose debris out of the combustion chamber.
  3. Rinse the heat exchanger with water or a solvent-free cleaner such as a citric acid based product.
  4. Use only a non-metallic brush with gentle strokes if needed.
  5. Do not use chemicals on the heat exchanger surface.
  6. Keep water away from the refractory.
  7. Flush the combustion chamber until water runs clear through the condensate trap.
  8. Clean out debris from the condensate trap and reinstall it.
  9. Do not scratch flue-gas contact surfaces; do not let tools or objects fall into the chamber.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 73. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.