Weil-McLain · Boiler troubleshooting

Direct exhaust sidewall termination, general rules

Ultra Series 4

What is going on

Installer-supplied termination. Bird screen is not included and must be bought separately. Keep the termination away from anything that can knock it or block it. Never tie another appliance or a second boiler into the same vent pipe.

Check in this order

  1. Insert a bird screen into the termination elbow before installing it.
  2. Place the termination where stones, balls, leaves or sediment cannot damage or block it.
  3. Do not connect any other appliance to the vent pipe.
  4. Do not connect multiple boilers to one common vent pipe.
  5. When several boilers vent to the outside, terminate each one separately and space the terminations for service access.
  6. Seal exterior openings with exterior caulk.
  7. Do not leave more exposed vent pipe outside the building than the manual shows, because condensate can freeze and block it.

Applies to: Ultra direct exhaust sidewall venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.