Weil-McLain · Boiler troubleshooting
Thermostat circuit voltage check
What is going on
There must never be any voltage across the boiler thermostat terminals. Voltage here will damage the control. A common cause is 3-wire zone valves wired incorrectly.
Likely causes
- External wiring error, often from 3-wire zone valves
Check in this order
- Disconnect the two external wires from the boiler thermostat terminals.
- Connect a voltmeter across the two incoming wires.
- Close each thermostat, zone valve and relay in the external circuit one at a time and read the voltage.
- If any voltage appears, correct the external wiring before reconnecting.
- Reconnect the wires and let the boiler cycle.
Applies to: SlimFit Series 2 wiring
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.