Weil-McLain · Boiler troubleshooting

Thermostat circuit voltage check

SlimFit Series 2

What is going on

There must never be any voltage across the boiler thermostat terminals. Voltage here will damage the control. A common cause is 3-wire zone valves wired incorrectly.

Likely causes

  • External wiring error, often from 3-wire zone valves

Check in this order

  1. Disconnect the two external wires from the boiler thermostat terminals.
  2. Connect a voltmeter across the two incoming wires.
  3. Close each thermostat, zone valve and relay in the external circuit one at a time and read the voltage.
  4. If any voltage appears, correct the external wiring before reconnecting.
  5. Reconnect the wires and let the boiler cycle.

Applies to: SlimFit Series 2 wiring

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.