Viessmann · Boiler troubleshooting
LON wiring, Vitocontrol-S CT3/VD2A or Vitotronic 300-K MW1B
What is going on
Wiring layout for the 120VAC and 24VAC gateway on a Vitocontrol-S CT3/VD2A or Vitotronic 300-K MW1B. The 300-K needs the LON card fitted.
Check in this order
- Install the LON communication card in the Vitotronic 300-K (required).
- Plug the 3 ft CAT-5 cable into the control's RJ45 socket and the other end into the gateway's internal RJ45 socket.
- Wire the LON 2-wire BMS connection to gateway terminals A and B.
- For 120VAC, use the plug-in power cord. For 24VAC, use a field-supplied 24VAC supply.
Applies to: Vitocontrol-S CT3/VD2A, Vitotronic 300-K MW1B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 501 and 501D LON gateway manual, p. 10-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.