Refrigeration systems: keep chilled water out of the boiler

CGi Series 5

What is going on

Chilled medium must not enter the boiler. Pipe the cooling system in parallel with the boiler.

Check in this order

  1. Pipe the chilled medium in parallel with the heating boiler.
  2. Install balancing and check valves so chilled medium cannot enter the boiler (see Figure 24).
  3. If the boiler feeds coils in air handlers that can see refrigerated air, add flow control valves or other automatic means to stop gravity circulation during cooling.

Applies to: CGi-25 to CGi-8 boilers connected to refrigeration or cooling systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGi Series 5 boiler manual, p. 37. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.