Weil-McLain · Boiler troubleshooting

Check if a reservoir pipe is needed on a steam return

EG / PEG Series 7

What is going on

Modern steam boilers steam for less time than older boilers. If the condensate return takes longer than the steaming time, the boiler can overfill with an auto feed or cycle off on a low water cutoff. Use this test on an existing residential system to find out whether a reservoir pipe is needed.

Likely causes

  • Condensate return time is longer than the boiler steaming time on a replacement boiler

Check in this order

  1. Disconnect the condensate return line at the existing boiler.
  2. Heat the boiler and let it steam for 10 minutes, then turn it off.
  3. Measure the time from when the boiler starts steaming to when condensate begins to return.
  4. Measure the time from when condensate starts returning to when it stops; divide this time by 2.
  5. Add the time from the first measurement to the calculated value. This is the average condensate return time.
  6. If the total is 10 minutes or less, no reservoir pipe is needed.
  7. If the total is more than 10 minutes, install a reservoir pipe as shown in Figure 23, sized from Table 8.
  8. For larger systems listed in Table 8, use a boiler feed system with a condensate tank and feed pump, sized from Table 9.

Applies to: Residential EG/PEG steam boilers during replacement

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.