Viessmann · Boiler troubleshooting
Burner not running and boiler cold (no fault shown on display)
What is going on
Fault behaviour with no code on the programming unit. Work through the cases by what the display and pumps are doing.
Likely causes
- No power to the Power Pump Module
- Low water cut-off device open (if installed)
- Faulty interconnection between Vitotronic and Power Pump Module
- Blown fuse F1 in the Vitotronic
- Pump fuses F1 to F4 in the Power Pump Module
- Open fixed high limit or other safety high limit
- Faulty burner connection cable or burner equipment (fuses, ignition module, venting equipment, motor-controlled flue damper)
Check in this order
- Turn the emissions test switch to the position shown in the manual.
- If the programming unit display is blank check power to the Power Pump Module, check the low water cut-off (if fitted), check the interconnection between Vitotronic and Power Pump Module, and check and replace fuse F1 in the Vitotronic if needed.
- If the display is on but no pumps run check the interconnection to the Power Pump Module and check fuses F1 to F4 in the module. Replace the fuse and pump if needed.
- If the display is on and pumps run measure voltage between L1 and N at the burner connector. If there is none, check the connector, burner connection cable and fixed high limit, and any other safety high limits (low water cut-off, pressure gauge).
- If voltage is present at L1 and N measure voltage at the burner terminal with the connector connected. If there is none, check the equipment on the burner (fuses, ignition module, venting equipment).
- If voltage is present at the burner terminal: press the TUV TEST button. The burner should start after a delay (for example oil preheat). If it still does not run, repeat the checks.
- Check any defective additional equipment that could block burner start, such as a motor-controlled flue gas damper.
Applies to: Vitotronic 200 KW2 burner start
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 200 service instructions, p. 41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.