Weil-McLain · Boiler troubleshooting

Water chemistry and inhibitor check

SlimFit Series 2

What is going on

Weil-McLain recommends adding Sentinel X100 inhibitor to protect the heat exchanger. Check water chemistry after filling and leak testing, and again at least once a year. Water pH must stay between 7.0 and 8.5, or the inhibitor test kit must show an acceptable level.

Likely causes

  • Residual substances left in the system after filling
  • Low inhibitor level or pH outside 7.0 to 8.5

Check in this order

  1. After filling and leak testing, check water pH and chlorine concentration.
  2. Add X100 inhibitor by caulking gun or in liquid form, following the container instructions.
  3. Let the water circulate, then test the inhibitor level with the Sentinel test kit and add more if needed.
  4. Each year, test pH of a system water sample; it must be 7.0 to 8.5.
  5. If pH is out of range or the test kit shows low inhibitor, correct the level before leaving the system.

Applies to: SlimFit Series 2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.