Weil-McLain · Boiler troubleshooting
Water chemistry and inhibitor check
What is going on
Weil-McLain recommends adding Sentinel X100 inhibitor to protect the heat exchanger. Check water chemistry after filling and leak testing, and again at least once a year. Water pH must stay between 7.0 and 8.5, or the inhibitor test kit must show an acceptable level.
Likely causes
- Residual substances left in the system after filling
- Low inhibitor level or pH outside 7.0 to 8.5
Check in this order
- After filling and leak testing, check water pH and chlorine concentration.
- Add X100 inhibitor by caulking gun or in liquid form, following the container instructions.
- Let the water circulate, then test the inhibitor level with the Sentinel test kit and add more if needed.
- Each year, test pH of a system water sample; it must be 7.0 to 8.5.
- If pH is out of range or the test kit shows low inhibitor, correct the level before leaving the system.
Applies to: SlimFit Series 2 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.