Weil-McLain · Boiler troubleshooting

Inspect and clean burners and base

EGPEG

What is going on

Check burners and base components. Clean burners if needed.

Likely causes

  • Dust, lint or debris blocking burner ports
  • Damaged base insulation

Check in this order

  1. Turn off power to the boiler, then remove the jacket door and base access panel.
  2. Inspect the burners and all other components in the base.
  3. If the burners need cleaning, raise the rear of each burner to free it from the support slot, slide it forward and remove it.
  4. Brush and vacuum the burners and confirm all ports are clear.
  5. Reinstall all burners, placing the burner with the pilot bracket in its original position and all burners upright with ports up.
  6. Confirm the base insulation is intact and secure on all four sides and the attachment clips are in place.

Applies to: EG and PEG Series 7 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 69. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.