Weil-McLain · Boiler troubleshooting
Inspect and clean burners and base
What is going on
Check burners and base components. Clean burners if needed.
Likely causes
- Dust, lint or debris blocking burner ports
- Damaged base insulation
Check in this order
- Turn off power to the boiler, then remove the jacket door and base access panel.
- Inspect the burners and all other components in the base.
- If the burners need cleaning, raise the rear of each burner to free it from the support slot, slide it forward and remove it.
- Brush and vacuum the burners and confirm all ports are clear.
- Reinstall all burners, placing the burner with the pilot bracket in its original position and all burners upright with ports up.
- Confirm the base insulation is intact and secure on all four sides and the attachment clips are in place.
Applies to: EG and PEG Series 7 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.