Viessmann · Boiler troubleshooting
Check or replace the plate type heat exchanger (CombiPLUS)
What is going on
Check the DHW side for scale and the heating water side for contamination. Clean or replace the plate type heat exchanger as needed.
Likely causes
- Scaling on the DHW side
- Contamination on the heating water side
Check in this order
- Shut off and drain the boiler on the heating water and DHW sides.
- Disconnect the diverting valve motor connection.
- Push the three-way valve drive A slightly upwards.
- Turn the three-way valve B with drive A 1/8 turn counterclockwise and remove it.
- Remove the two screws C from the plate type heat exchanger and remove the heat exchanger D with its gaskets. Small amounts of water may trickle out.
- Check the DHW side for scaling. Clean or replace the heat exchanger if required.
- Check the heating water side for contamination. Clean or replace the heat exchanger if required.
- Install in reverse order with new gaskets. Refer to the installation instructions for additional mounting options.
Applies to: CombiPLUS plate type heat exchanger
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.