Connecting the Vitotrol 200A to the boiler control

Vitotrol 200A

What is going on

Connect the two-wire communication cable from the remote to the control unit. The remote can connect to a 2- or 3-pole plug on the Vitotronic control unit or KM BUS distributor, or to an EA1 module or external accessory connection box, depending on the system. Use the connection diagrams in the manual for the specific system.

Check in this order

  1. Touch a grounded object to discharge static before handling electronics.
  2. Run the two-wire, 21 AWG cable to the remote, keeping it away from 120 V and other high-voltage wiring.
  3. Connect the cable to the 2- or 3-pole plug on the control unit or KM BUS distributor, or to the EA1 module or accessory box as the system diagram shows.
  4. Keep the total cable length within 150 ft (50 m).

Applies to: Vitotrol 200A with Vitotronic control unit, EA1 module or external accessory connection box

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotrol 200A installation, operating and service instructions, p. 5. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.