Checking boiler temperature sensors
What is going on
Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors are all resistance type. Compare measured resistance with the sensor resistance table.
Likely causes
- Sensor out of range versus the resistance table
- Control reading a temperature that does not match the input resistance
Check in this order
- Set an ohmmeter and measure sensor resistance at known temperatures: ice point (32°F), room temperature (60°F and 70°F) and boiling point at sea level (212°F).
- For ice point and boiling point, submerge the sensor in water at that temperature.
- For dual sensors, make sure the temperature difference between the two sensors is no more than 10°F.
- Compare the reading against the sensor resistance table. The table does not list 212°F.
- To check control sensing, connect a resistance decade box temporarily in place of a sensor and read the temperature on the control display. It should match the value for that resistance.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 160. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.