Weil-McLain · Boiler troubleshooting

Checking boiler temperature sensors

ECO Tec Series 3

What is going on

Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors are all resistance type. Compare measured resistance with the sensor resistance table.

Likely causes

  • Sensor out of range versus the resistance table
  • Control reading a temperature that does not match the input resistance

Check in this order

  1. Set an ohmmeter and measure sensor resistance at known temperatures: ice point (32°F), room temperature (60°F and 70°F) and boiling point at sea level (212°F).
  2. For ice point and boiling point, submerge the sensor in water at that temperature.
  3. For dual sensors, make sure the temperature difference between the two sensors is no more than 10°F.
  4. Compare the reading against the sensor resistance table. The table does not list 212°F.
  5. To check control sensing, connect a resistance decade box temporarily in place of a sensor and read the temperature on the control display. It should match the value for that resistance.

Applies to: 80/110/150/199 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 160. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.