Weil-McLain · Boiler troubleshooting

Condensate trap has dried out (flue gas at drain)

CGa Series 4CGi Series 5EG Series 7PEG Series 7LGB Series 2 & 3

What is going on

With the boiler running, flue gas coming out of the condensate drain means the trap is dry and must be refilled. Flue gas in the room is a safety hazard.

Likely causes

  • Vent system not making enough condensate to keep the trap full
  • Obstruction in the condensate drain line

Check in this order

  1. Make sure the boiler is running and hold a finger near the drain tube outlet to feel for flue gas.
  2. Remove the trap and pour fresh water into it until water runs out the far end of the drain line.
  3. If no water comes out, there is a blockage: loosen the flexible drain hose and trap inlet connection.
  4. Remove and flush the trap and drain line, then reinstall and tighten all connections.
  5. Pour water in again and confirm it runs out the drain end.
  6. If water still does not come out, call a qualified technician to clean or replace the condensate assembly.
  7. If the trap dries out regularly, have a technician inspect the boiler and condensate line.

Applies to: Models with condensate drain system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.