Viessmann · Boiler troubleshooting

Connecting the boiler control to a LON system

Vitodens 200-W

What is going on

Boiler control is linked to Vitotronic 200-H mixing valve controls and a Vitocom LON module. The LON communication module is an accessory and must be installed. Data transfer can take several minutes. Only one Vitotronic can be the fault manager, and each participant number can be used only once in the same LON system.

Check in this order

  1. Install the LON communication module (see its installation instructions).
  2. Set LON participant numbers and functions in coding level 2 (see LON table).
  3. Set exactly one control as fault manager (code 79:1). All others use 79:0.
  4. Set the time transmitter and receiver codes (7B:1, 81:3).
  5. Set the outside temperature transmitter and receiver codes (97:2, 97:1).
  6. Set LON participant fault monitoring (9C:20) on the mixing valve controls.
  7. Wait several minutes for the data transfer.
  8. Run the LON participant check.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 41-42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.