Viessmann · Boiler troubleshooting
Thermostat, off-peak and secondary pump wiring
What is going on
Call-for-heat and off-peak inputs use voltage-free contacts. A secondary pump can be run from Pump 2.
Check in this order
- Use voltage-free (dry contact) switches from a thermostat, valve end switches or zone panel.
- Run 2 x 18 gauge wire from the thermostat to the TT terminals.
- Keep the thermostat away from other heat sources.
- For off-peak control, connect a voltage-free contact to OP. Keep the blue/white jumper in place if it is not used.
- Connect an optional secondary pump to Pump 2. It starts when the thermostat contacts close.
Applies to: Vitotron 100 VLN2 controls
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotron 100 VLN2 installation and service instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.