Weil-McLain · Boiler troubleshooting

No spark, system does not work (with vent damper, Chart 2)

EG / PEG Series 7

What is going on

Troubleshooting chart for a no-spark condition on steam boilers with a vent damper. Flowchart text is out of order in the extracted pages; the steps follow the chart's checks.

Likely causes

  • Damper harness not securely plugged in
  • Damper actuator faulty
  • Damper wiring harness open
  • Ground or spark components faulty
  • Open thermostat, circulator relay, spill switch, rollout fuse, LWCO or high limit contacts

Check in this order

  1. Turn off supply voltage before checking connections.
  2. Check that the damper harness is securely plugged in at both ends.
  3. Check for 24 VAC across terminals PV and MV/PV.
  4. Check for 24 VAC across terminals C and Y on the transformer. If absent, check for loose wire connections or a bad relay on the transformer.
  5. Check for 24 VAC between C and the yellow wire between the damper connector and the rollout thermal fuse element.
  6. Check whether the damper is rotated open. Open the thermostat contacts for 30 seconds; the damper should rotate closed. Close the thermostat contacts; the damper should rotate open.
  7. If the damper does not move, check for an out-of-round stack section. Check whether the motor rotates open; if not, replace the actuator.
  8. Check continuity of each wire in the damper harness. Replace the damper wiring harness if any wire is open.
  9. Temporarily install a jumper between terminal 2 and terminal 5 on the damper plug in the boiler wiring harness. If the boiler fires, the damper circuit is at fault; remove the jumper afterward.
  10. Recheck spark verify the spark wire, electrode ceramic and spark gap (0.125 in) as in Chart 1, then replace components as indicated and run several complete cycles.

Applies to: EG and PEG steam boilers with vent damper

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 79. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.