Weil-McLain · Boiler troubleshooting
No spark, system does not work (with vent damper, Chart 2)
What is going on
Troubleshooting chart for a no-spark condition on steam boilers with a vent damper. Flowchart text is out of order in the extracted pages; the steps follow the chart's checks.
Likely causes
- Damper harness not securely plugged in
- Damper actuator faulty
- Damper wiring harness open
- Ground or spark components faulty
- Open thermostat, circulator relay, spill switch, rollout fuse, LWCO or high limit contacts
Check in this order
- Turn off supply voltage before checking connections.
- Check that the damper harness is securely plugged in at both ends.
- Check for 24 VAC across terminals PV and MV/PV.
- Check for 24 VAC across terminals C and Y on the transformer. If absent, check for loose wire connections or a bad relay on the transformer.
- Check for 24 VAC between C and the yellow wire between the damper connector and the rollout thermal fuse element.
- Check whether the damper is rotated open. Open the thermostat contacts for 30 seconds; the damper should rotate closed. Close the thermostat contacts; the damper should rotate open.
- If the damper does not move, check for an out-of-round stack section. Check whether the motor rotates open; if not, replace the actuator.
- Check continuity of each wire in the damper harness. Replace the damper wiring harness if any wire is open.
- Temporarily install a jumper between terminal 2 and terminal 5 on the damper plug in the boiler wiring harness. If the boiler fires, the damper circuit is at fault; remove the jumper afterward.
- Recheck spark verify the spark wire, electrode ceramic and spark gap (0.125 in) as in Chart 1, then replace components as indicated and run several complete cycles.
Applies to: EG and PEG steam boilers with vent damper
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, p. 79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.