Mixing valve rotation check
What is going on
During an actuator test of a mixing valve, the supply temperature must rise when the valve opens. If it drops, the motor is turning the wrong way or the mixing valve set is fitted incorrectly.
Likely causes
- Motor rotating in wrong direction.
- Mixing valve set incorrectly fitted.
Check in this order
- Run the mixing valve Open actuator test.
- Watch the supply temperature. It must rise.
- If it drops, check the motor rotation direction.
- Check the mixing valve set fitting against the mixing valve installation instructions.
Applies to: Heating circuits with mixing valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 Dual Fuel service instructions, p. 118. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.