Install boiler safety devices and pressure relief discharge piping

Vitocrossal 300 CU3A

What is going on

Fit the factory pressure relief valve and air vent, then run the discharge pipe to a floor drain. The discharge must never go outdoors.

Check in this order

  1. Apply pipe sealant to both ends of fittings B, D, F and G, then fit them into coupling A and tees C.
  2. Install the pressure relief valve H and the air vent E and tighten both.
  3. Run the relief discharge pipe with an unthreaded end, and end it about 6 in. (150 mm) above the floor drain.
  4. Do not fit any shutoff valve in the discharge pipe, do not reduce its diameter (minimum 3/4 in.), and do not fit an isolation valve between the boiler and the relief valve.
  5. Position the discharge so it cannot scald anyone nearby.

Applies to: Vitocrossal 300 CU3A 26 to 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.