Weil-McLain · Boiler troubleshooting

Hang the boiler on the wall bracket

ECO Tec Series 3

What is going on

Lift the boiler so its mounting bracket clears the wall bracket, then lower it until the brackets engage.

Check in this order

  1. Mark a line or place masking tape 17 1/2 inches below the bottom edge of the wall-mount bracket; the boiler bottom should sit at this mark when seated.
  2. Use two people. Wear non-slip leather gloves.
  3. Lift only by the bottom and rear of the sheet metal housing, never by a pipe or plastic part. The jacket door may stay on.
  4. Lift the boiler high enough that its mounting bracket is above the wall bracket.
  5. Lower the boiler so the rear slides against the wall bracket until the brackets are fully engaged and the boiler is in position.
  6. Confirm the bracket is engaged and not just resting on the edge of the wall bracket. If not, the boiler could fall.
  7. Check that the boiler is level front to back. Do not pitch it forward, because that stops condensate from draining.

Applies to: Wall mount installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 14-15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.