Viessmann · Boiler troubleshooting
Check flue gas collector seals, lip seal and insulation
What is going on
Look for leaks at the flue gas collector and the boiler flue connection. Condensate on the outside of the collector also indicates a leak.
Likely causes
- Worn or loose flue gas collector gasket
- Leaking lip seal at the boiler flue connection
- Water side fitting leak
- Damaged or loose thermal insulation
Check in this order
- Check the gasket/seal between flue gas collector C and boiler body B for tightness.
- Check lip seal D on the boiler flue connection.
- Under full load, use an inspection mirror if needed. Remove thermal insulation parts if required.
- Before removing the flue gas collector, unplug flue gas temperature sensor F.
- If the collector seal leaks, retighten it at tensioning toggles E or replace it.
- Replace lip seal D if it leaks.
- Check water side fittings and replace seals or gaskets if needed.
- Check that the boiler insulation fits well. Correct the fit or replace damaged parts.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.