Weil-McLain · Boiler troubleshooting

Cleaning the CGa temperature/LWCO sensor probe

Weil-McLain CGa Series 4

What is going on

Deposits on the probe affect the water temperature and low water readings. Clean it once a year.

Likely causes

  • Scale or dirt on the probe and insulator

Check in this order

  1. Turn off power to the boiler before unplugging connectors or measuring resistance.
  2. Unplug the harness from the sensor.
  3. Drain the boiler below the sensor and remove the sensor.
  4. Wipe the build-up off the probe and the insulator.
  5. Reinstall with suitable thread sealant. Do not over-tighten.
  6. Refill, purge air and check for leaks. Then test the LWCO with the LWCO TEST button.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Service and maintenance - Temperature/LWCO sensor, p.59. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.