Weil-McLain · Boiler troubleshooting
Cleaning the CGa temperature/LWCO sensor probe
What is going on
Deposits on the probe affect the water temperature and low water readings. Clean it once a year.
Likely causes
- Scale or dirt on the probe and insulator
Check in this order
- Turn off power to the boiler before unplugging connectors or measuring resistance.
- Unplug the harness from the sensor.
- Drain the boiler below the sensor and remove the sensor.
- Wipe the build-up off the probe and the insulator.
- Reinstall with suitable thread sealant. Do not over-tighten.
- Refill, purge air and check for leaks. Then test the LWCO with the LWCO TEST button.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Service and maintenance - Temperature/LWCO sensor, p.59. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.